Rpba Installation Guide
This Document serves as a guide for the installation of an Rpba inside the boundary of Water District #20. All installations must be inspected and approved by the Districts Cross-Connection Control Specialist. Please contact the District within 2 business days to schedule an inspection.
​
-
Assembly shall be installed on the customers side of the meter prior to any branch or tee on the service line.
-
An Rpba shall be installed in the orientation for which it is approved. (E.G. horizontal/vertical) either orientation shall have the relief valve installed horizontally.
-
Insulation shall not obstruct relief valve from discharging to atmosphere
-
Install Assembly according to the manufacturers specifications.
-
Assembly must be installed above ground in a heated or insulated enclosure.
-
Water District #20 highly recommends freeze protection. (Insulation or padded wraps)
-
Assemblies greater than 2 1/2" shall be supported to protect the flange from damage.
-
Assembly shall be installed a min. of 12" above grade measured from the relief vent.
-
Installed Assembly shall be rigid and stable
-
Installed Assembly should be easily accessible for testing and maintenance.
-
There shall be 2 drain holes equal in size to the relief vent.
Ball shut off valve
Union
Type "K" copper
= to dia. of RPBA
1' min
3' max